The Larson Electronics MPD-CD2-BSF-YE45YT-GC-12.N10-M1 temporary power distribution system converts three-phase 480V AC electrical current into three-phase 208Y/120V AC. This unit provides operators the ability to safely tap into and distribute 480V AC power from a variety of sources including generators and direct grid power.

*PLEASE NOTE: ANY FREE SHIPPING OFFERS DO NOT APPLY TO POWER DISTRIBUTION PANELS, TRANSFORMERS, OR SUBSTATIONS*

The MPD-CD2-BSF-YE45YT-GC-12.N10-M1 temporary power distribution system gives operators the ability to power their 480 volt, 208 volt and 120 volt equipment from a single system. On the primary side, operators connect 480 volt line-in power via 150` of #2 SOOW cord and to one 520R7W receptacle for 480Y/277V equipment. On the secondary side, operators connect to one 4100R12W and one 530R9W receptacles for 208Y/120V equipment, as well as to twelve duplex GFCI receptacles for 120V equipment. There is also 30` of #12 SOOW cord on the secondary side for 208Y/120V output connections.

Operation: A 150` #2 SOOW line-in cord brings three-phase 480V AC power to the primary side, which contains one 60-amp 3-pole 480V breaker and one 20-amp 3-pole 480V breaker protecting one 20-amp 520R7W 480Y/277V receptacle, and passes power through to the transformer. The NEMA 3R 45KVA transformer converts 480V to three-phase 208Y/120V 60Hz and passes the current to the secondary panel. The secondary side of the transformer feeds a NEMA 3R 125-amp, three-phase 208Y/120V main lug only panel. This secondary panel contains one 30-amp 3-pole 250V breaker protecting one 100-amp 4100R12W 125/250V receptacle, one 30-amp 2-pole 250V breaker protecting one 30-amp 530R9W 120/208V receptacle and twelve 20-amp 1-pole 125V breakers protecting twelve 20-amp duplex GFCI 125V receptacles. Operators may also access one 20-amp 1-pole 125V breaker and one 30` #12 SOOW cord on the secondary side for output connections.


Click Photo to Enlarge

Protective Construction: The transformer and load center/distribution assembly is mounted to a standard steel cart style frame resulting in an extremely stable, durable, and mobile power distribution platform. Two rubber tires and a cart style mounting platform provides easier substation mobility, and a center point lift eye allows easy lifting with cable or chain hooks. This temporary power distribution solution can be modified to meet the needs of job-site receptacle requirements. Larger units are available upon request and can be equipped with skids or trailer mounted.

Certification: All units are built in accordance to NFPA 70 (National Electric Code) and certified to UL 1640. All equipment is NEMA 3R rated for indoor and outdoor use and provide a degree of protection against dirt, water, and ice. NEMA 4 and NEMA 4X equipment can be equipped upon request.

Grounding: Transformer is grounded to the frame and we provide a grounding lug on the frame for the earth ground.
~Please check all motor loads for dual rated motors that will work 208 or 240.~


Applications:

This power distribution system is NEMA 3R rated and ideal for indoor/outdoor use and applications including but not limited to; construction sites, plant maintenance, plant turnarounds, shows, exhibits and shipyard operations.

Larson Electronics is a manufacturer and as such can build portable transformer systems to your specifications. Although we carry several models of power distribution transformers, we can deliver custom ordered units almost as quickly as our prebuilt units. If this model does not meet your needs, please contact us at 1-800-369-6671 or [email protected] to discuss your specific requirements.