Fluke i2000 Flex AC Current Clamp
The i2000 is an AC current probe utilizing the Rogowski principle. It can be used to measure currents up to 2000 A when used in conjunction with multimeters, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.
Key features
- Three ranges: 20A, 200 A & 2000 A, 100 mV/A, 10 mV/A & 1 mV/A output
- Ideal for current measurement on thick and hard to reach conductors without breaking the circuit
- Maximum conductor diameter 178 mm
- CAT III 600 V safety rating
Electrical specifications | |
Current ranges | 20 A 200 A 2000 A AC rms |
Output sensitivity (AC-coupled) | 1 mV 10 mV 100 mV 1 mV per A |
Load impedance | 100 k½ minimum |
Accuracy | at +25¡C ±1% of range (45 Hz to 65 Hz) |
Linearity | 10% to 100% of range ±0.2% of reading |
Noise | 8 mV AC rms (30 A) 2 mV AC rms (300 A, 3000 A) |
Frequency range | 10 Hz to 20 kHz (-3 dB) |
Phase error | < ±1¡ (45 Hz to 65 Hz) ±10¡ (at 20 kHz) |
Position sensitivity (with cable > 25 mm from the coupling) | Position sensitivity: From 1% up to 3% of range with cable, depending on distance from the center (see figure left). Measurements closer than 25 mm from the coupling are typically greater than 3% of range. |
External field | with cable > 200 mm from the head ±1% of range |
Power supply | 2 x AA/MN 1500/LR6 Alkaline, 200 hours, low battery indicator |
Temperature Coefficient | ±0.08% of reading per ¡C |
Working voltage | see Safety standards section 600 V AC rms or DC |
General Specifications | |
Head Circumference | 610 mm (24 in) |
Head cable diameter | 14.3 mm (0.56 in) |
Head bend radius | 38.1 mm (1.5 in) |
Cable length (head to electronics) | 2 m (6.56 ft) |
Output connection | Molded 4 mm safety plugs (not integrated) |
Operating temperature range | 0¡C to +70¡C (32¡F to 158¡F) (head and electronics) |
Storage temperature range | -40¡C to +105¡C (-40¡F to 221¡F) (head) -20¡C to +85¡C (-4¡F to 185¡F) (electronics) |
Operating humidity | 15% to 85% (non-condensing) |
Weight | 180 g (6.34 oz) (head) 190 g (6.70 oz) (electronics) |
Safety standards | EN 61010-031: 2002 EN 61010-2-032: 2002 EN 61010-1: 2001 600 Vrms, Category III, Pollution Degree 2 Use of the probe on uninsulated conductors is limited to 600 V ac rms or dc and frequencies below 1 kHz. |
EMC standards | EN 61326: 1998 +A1, A2, and A3 |
Dimensions (H x W x D) | 116 x 68.5 x 30 mm (4.56 x 2.69 x 1.18 in) |