SensorSwitch 88256 High Bay Aisleway, Surface, Line Volt, PIR HMR 50 Sensor
The HMR 50 Series sensor provides Bi-Directional High Bay Aisle Way sensing extending 70 to 110 ft when mounted at heights of 30 to 45 ft. HID Bi-Level or T5 / T8 Fluorescent systems can be switched directly using this sensor without the use of power packs. The HMR 50 SH controls Bi-Level HID with a Start-to-High timer, whereas the HMR 50 controls individual fluorescent fixtures. The sensor's view pattern provides coverage of the lighting areas of three typically spaced High Bay fixtures. Therefore, when mounted at a fixture, the coverage area extends out to the area that is lighted by the neighboring fixtures. This effect is useful with some Program-Start ballasts that have a delay such that when traveling in a fork-lift truck, lighting needs to be initiated On ahead of the truck. Masking the sensor to cutoff at the end of an aisle is easily done with the enclosed kit. For freezer or high humidity applications, use the HMR 50 LT or HMR 50 SH LT which allows for cold temperatures or condensing humidity. For total aisle way sensing consider the HMR 10 at each end, and HMR 50s in the center section. PIR Occupancy Detection Up to 45 ft Mounting Bi-directional Aisle Way Sensing Pattern (70-110 feet) Self-Contained Relay - No Power Pack needed No Minimum Load Requirements Time Delay: 75 sec to 20 min Green LED Indicator