Type 2 3-Phase Surge Panel with Enhanced Noise Filtering
277/480V 220/380V 3-Phase WYE, 240V 480V 3-Phase Delta, Surge Panel, Enhanced Noise Filtering, NEMA 3R Enclosure, UL 1449 4th Edition Type 2
LevitonÕs Surge Protection Devices can be used individually or as part of a coordinated application strategy, to protect sensitive electronic equipment, in industrial, commercial and residential locations, from the stress and degradation inflicted by voltage transients. Leviton Surge Protection Devices are compliant with UL 1449 Standards. LevitonÕs outstanding Surge Protection Devices divert damaging voltage transients, or surges, away from electronic equipment. Transients are diverted away from sensitive micro circuitry, providing protection against catastrophic failure, costly downtime and data disruptions.
Frequency: 50/60Hz
Recommended Circuit Breaker Rating: 30A, 277/480V
Surge Technology: 40mm MOV Design
Voltage Configuration: 220/380 V or 277/480 V, 3-Phase WYE; 240 V or 480 V, 3-Phase Delta
Flammability: Rated V-2 per UL 94
Operating Temperature: -10¡C to 60¡C
Relative Humidity: 5% to 95% non-condensing
Storage Temperature Range: -20C to 85C
Diagnostics: LED
Remote Monitoring: Dry Contact Leads-N.O./N.C. Form C Rated at 7Amps @ 240VAC or 30 VDC
Surge Counter: No
MCOV L-L: 552
MCOV N-G: 320
Maximum Surge Current, Per Mode (Per Phase): 80kA (160kA)
Nominal Discharge Current Rating: 3kA
Short Circuit Current Rating: 100kA
VPR L-G: 2000
VPR L-L: 1800
VPR L-N: 1200
VPR N-G: 1200
MCOV: 320V AC
Noise Rejection: -30 to -40 dB at 10kHz-10MHz
Replaceable Modules: No
UL1449 Impluse 6kV/500A L-N/N-G/L-L: 900/800/1500
UL 1449 4th Edition: cULus Listed Type 2
Frequency: 50/60Hz
Recommended Circuit Breaker Rating: 30A, 277/480V
Surge Technology: 40mm MOV Design
Voltage Configuration: 220/380 V or 277/480 V, 3-Phase WYE; 240 V or 480 V, 3-Phase Delta
Flammability: Rated V-2 per UL 94
Operating Temperature: -10¡C to 60¡C
Relative Humidity: 5% to 95% non-condensing
Storage Temperature Range: -20C to 85C
Diagnostics: LED
Remote Monitoring: Dry Contact Leads-N.O./N.C. Form C Rated at 7Amps @ 240VAC or 30 VDC
Surge Counter: No
MCOV L-L: 552
MCOV N-G: 320
Maximum Surge Current, Per Mode (Per Phase): 80kA (160kA)
Nominal Discharge Current Rating: 3kA
Short Circuit Current Rating: 100kA
VPR L-G: 2000
VPR L-L: 1800
VPR L-N: 1200
VPR N-G: 1200
MCOV: 320V AC
Noise Rejection: -30 to -40 dB at 10kHz-10MHz
Replaceable Modules: No
UL1449 Impluse 6kV/500A L-N/N-G/L-L: 900/800/1500
UL 1449 4th Edition: cULus Listed Type 2