Fluke 1664 FC Multifunction Installation Tester helps expedite installations
The 1664 FC puts a lot of testing power in your hands to quickly and efficiently test to all local regulations, protect appliances, and share test results in real time over your smartphone.
Protect appliances from accidental damage
The Fluke 1664 FC is the only tester with "Insulation PreTest" that stops the insulation test and provides a visual warning if it detects that an appliance is connected to the system under test. This helps you avoid potentially serious and costly mistakes that can cause damage to your customersÕ peripheral equipment.
Auto Test reduces test time
Auto Test performs up to seven installation tests in one sequence, ensuring compliance with local installation regulations. This reduces the number of manual connections, thus decreasing the possibility of errors and reducing test time.
Save time and enhance collaboration
Because the 1664 FC is Fluke Connect¨-enabled, you can send test results to your smartphone, save them to the cloud, and share measurements in real time with team members through a ShareLive video call. It's the fastest way to let your team see what you see, and to help you get approvals without leaving the field.
Retrieve stored results from anywhere
Fluke Cloud storage allows you to retrieve stored results whether you are in the office or in the field to make decisions in real time. You get world-class data protection and you can import the data into Fluke DMS (Data Management Software) to process and generate certificates.
Other helpful features:
- Compact, lightweight (less than 1.3 kg) with padded neck-strap to free your hands
- Rotary dial knob clearly indicates which function is selected, all in one spot with no complex multi-level menus.
- Offers additional high current loop mode for faster measurements than loop tests with non-trip mode for RCDs
- Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
- Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
- Performs fast voltage measurement between L-N, L-PE, and N-PE using the mains cord. No need to change measurement connections
- Measures RCD trip current and trip time in parallel (RCD type AC and A)
- Measures PEFC or PSC and loop impedance in parallel and displays them together on the dual display
- Offers ring testing so you can select the required input sockets with soft keys and not have to exchange test leads
- Uses continuity test currents to measure motor windings
- Detects raised earth voltages > 50 V with Earth Volt Touchpad, indicating potential dangerous situations
- Features large display with backlight, clear symbols, and exceptionally wide viewing angle for easy and safe readings
- Offers extended three-layer memory
Key features
- Includes "Insulation Pre-test" that detects when appliances are connected to the system and stops the test
- Runs seven installation tests automatically in one sequence with a single connection through Auto Test
- Allows you to share test results in real time over your smartphone via Fluke Connect Measurements
AC voltage measurement | ||
Range | 500 V | |
Resolution | 0.1 V | |
Accuracy 45 Hz Ð 66 Hz | 0.8% + 3 | |
Input impedance | 360 k½ | |
Overload protection | 660 V rms | |
Continuity testing (RLO) | ||
Range (autoranging) | 20 ½ / 200 ½ / 2000 ½ | |
Resolution | 0.01 ½ / 0.1 ½ / 1 ½ | |
Open Circuit Voltage | >4 V | |
Insulation resistance measurement (RISO) | ||
Test voltages | 50-100-250-500-1000 V | |
Accuracy of tTest voltage (at rated test current) | +10%, -0% | |
Test voltage | 50 V 100 V 250 V 500 V 1000 V | |
Insulation resistance range | 20 M½ /50 M½ 20 M½ / 100 M½ 20 M½ / 200 M½ 20 M½ / 200 M½ / 500 M½ 20 M½ / 200 M½ / 1000 M½ | |
Resolution | 0.01 M½ / 0.1 M½ 0.01 M½ / 0.1 M½ 0.01 M½ / 0.1 M½ 0.01 M½ / 0.1 M½ / 1 M½ 0.01 M½ / 0.1 M½ / 1 M½ | |
Test current | 1 mA @ 50 k½ 1 mA @ 100 k½ 1 mA @ 250 k½ 1 mA @ 500 k½ 1 mA @ 1 M½ | |
Loop and line impedance (ZI) | ||
Range | 10 ½ / 0.001 ½ / High current m½ mode | |
Resolution | 0.01 ½ / 0.1 ½ / 1 ½ | |
Prospective earth fault current, PSC test | ||
Range | 1000 A / 10 kA (50 kA) | |
Resolution | 1 A / 0.1 kA | |
Computation | Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively. | |
RCD testing, RCD types tested | ||
RCD Type | AC_ G_,S_ | |
Model 1664 | A, AC, B5, S | |
Notes | _Responds to AC _General, no delay _Time delay 4Responds to pulsed signal 5Responds to smooth DC signal | |
Tripping speed test (_T) | ||
Current settings_ | 10-30-100-300-500-1000 mA Ð VAR 10-30-100 mA | |
Multiplier | x _, x 1 x 5 | |
Measurement range | RCD Type G | 310 ms 50 ms |
RCD Type S | 510 ms 160 ms | |
Notes | _1000 mA type AC only 700 mA maximum type A in VAR mode VAR mode not available for type B. | |
RCD/FI-Tripping Current Measurement/Ramp Test (I_N) | ||
Current range | 30% to 110% of RCD rated current_ | |
Step size | 10% of I_N_ | |
Dwell time | Type G | 300 ms/step |
Type S | 500 ms/step | |
Measurement accuracy | ±5% | |
Specified trip current ranges (EN 61008-1) | 50% to 100% for Type AC 35% to 140% for Type A (>10 mA) 35% to 200% for Type A (²10 mA) 50% to 200% for Type B _5% for Type B | |
Notes | _30% to 150% for Type A I_N > 10 mA 30% to 210% for Type A I_N = 10 mA 20% to 210% for Type B | |
Earth Resistance Test (RE) | ||
Range | 200 ½ / 2000 ½ | |
Resolution | 0.1 ½ / 1½ | |
Frequency | 128 Hz | |
Output Voltage | 25 V | |
Phase Sequence Indication | ||
Icon | ÊPhase Sequence indicator is active. | |
General Specifications | ||
Size (L x W x H) | 10 x 25 x 12.5 cm | |
Weight (incl. batteries) | 1.3 Kg | |
Battery size, quantity | Type AA, 6 ea. | |
Sealing | IP-40 | |
Safety | Complies with EN/IEC 61010-1 and EN/IEC 61010-2-034 | |
Overvoltage | CAT III / 500V; CAT IV 300V | |
Performance | EN61557-1 to EN61557-7 and EN61557-10 |