| Performance |
| Product Type | Emergency Unit |
| Description | Decorative Outdoor Die-Cast AC/Emergency Unit |
| Input Power | 2.8W |
| Lumens | 1,286lm AC; 350lm DC |
| Electrical |
| Power Factor | 0.3 |
| Input Voltage | Dual 120/277 Voltage |
| Frequencies | 50/60 Hz |
| Input Current @ 120V (mA) | 23mA |
| Input Current @ 277V (mA) | 10mA |
| Dual Voltage Circuit Operation | No |
| Operating Temperature | -4°F to 122°F (-20°C to 50°C) |
| Emergency Illumination | 90 minutes |
| Battery Type | Nickel Cadmium |
| Battery Voltage | 4.8V |
| Recharge Time Required | 24-hours |
| Battery Operating Temperature | -22°C to 122°C (-30°F to 50°F) |
| Storage Temperature | 68°F to 86°F (20°C to 30°C) |
| Storage Shelf Life | 3 years before the initial charge. 5 years after initial charge. |
| Self Diagnostics | Yes |
| Remote Test Switch | No |
| Installation |
| Mounting Method | Back |
| Mounting Type | Wall Mount |
| Maximum Mounting Height (ft.) | 30 ft |
| Emergency Egress Coverage(ft) Mounting at height of 7.5ft | 29 ft x 3 ft mounted @ 7.5 ft |
| Spacing Criteria for Emergency Egress | 45 ft on center assuming 7.5 ft mounting height with egress path 3 ft out |
| Cold Weather Rated | Yes |
| Construction |
| Shape | Rectangle |
| Housing Material | Die Cast Aluminum |
| Housing Color | Bronze |
| Remote Capacity | No |
| Compliance |
| Listings | UL924 Listed |
| Environment | Suitable for indoor or outdoor use in dry, damp, and wet environments |
| IP Rating | Indoor/Outdoor |
| Certification Model Number | DBEL-ACEM-HL-BR-SDT-PC-CW-CEC |
| T20 Compliant | Can be used to conform with the requirements of California Title 20 |
| California Title 24 JA8 Compliant | Not applicable |
| California Energy Commission (CEC) Status | Lawful for Sales in California |
| FCC | Complies with Part 15 of the FCC Rules |