Sunled Industries EM-EMS Split Emergency Driver 8-18W/Up to 200W

EM-EMSÊSeries

Split Emergency Driver

The EM-EMS series emergency LED driver is for field and factory installation that allows any Sunled 0-10V dimmable fixture to be used for both normal and emergency operation.

The unit contains a battery charger and inverter that operates a load of 8W or 18W with constant power at a rated output voltage of 170VDC. The patented constant power circuitry of the module maintains uninterrupted illumination levels during power failure

Ê

Armour logos3

Ê

  1. PRODUCT VARIATIONS
  2. FEATURES
  3. SELF DIAGNOSTIC
  4. OPERATION
  5. SPECIFICATIONS
  6. APPLICATIONS
Ê
Product Code

Example EM-EMS cat. 18.WW

ÊMODEL NO WATTAGE TEST SWITCH
EM-EMS 8 8W / 170VDCÊ WW Wired
Up to 100W Driver WL 2.4GHz Remote
18 18W / 170VDCÊ
Up to 200W Driver
Ê
NOTES
_ The emergency driver is not compatible with non-dimmable fixtures when the driver wattages is less than the fixture wattage.Ê
Ê
Features
Ê
  • Constant power output in emergency mode
  • Split two piece design with smaller dimensions for integral enclosures
  • Self-sensing output voltage circuitry maximises product compatibility
  • High temperature recyclable lithium battery technology enables significantly decreased enclosure size and longer operational life
  • Quick connect junction box on driver side reduces installation time
Ê
Self Diagnostic
Ê
The integrated self-diagnostic circuitry will automatically conduct 1 monthly 30 second and annual 90 minute tests to verify proper emergency capability per life safety code requirements NFPA 101ÊLife Safety Code outlines the following schedule:
Ê
Monthly
During AC mode, the system conducts a 30s self discharge test of the emergency LED driver every 30 days and automatically restores to normal charging after full discharge
Ê
Annually
During AC mode, the system conducts a 90 minute self discharge test of the emergency led driver every 365 days and automatically restores to normal charging after 30 seconds discharge
Ê
Operation
Ê
Normal Supply
During normal AC supply conditions the LED driver load will operate as usual and emergency driver remains in charging mode
Ê
Emergency Mode
When AC power fails the driver automatically switches to emergency mode, keeping the LED load illuminated at a reduced lumen output for a minimum of 90 minutes. During this time, the indicator will flash slowly (light on for 2 seconds, off for 2 seconds). When AC power is restored, it will return to charging mode and the indicator light remains on
Ê
Specification
Ê
Input Voltage: 120-347VAC 50/60Hz
Input Power: 7W Max
Output Voltage: 170VDC
Input Current: 100mA
Output Power: 8,18W Power Factor: 0.85
EMI Radiated/Conducted: FCC Class A Charge and EM Modes
Surge Protection: Line-Neutral 3kV
Emergency Operation: 90 minutes
Charge Time: 24hr Recharge
Ambient Temperature: Lithium 5¡C to +50¡C (41¡F to 122¡F)
Approval: cUL Listed for Factory and Field Installation
Ê
Ê
Applications
Ê
Canopy, indoor and outdoor linear, wall pack
Ê