Sunled Industries EM-EMB High Output Emergency Driver 15-40W/Up to 300W

Sunled Industries

(No reviews yet) Write a Review
SKU:
SUNLED-EM-EMB
Weight:
0.00 LBS
Call for price
Sunled Industries EM-EMB High Output Emergency Driver 15-40W/Up to 300W

EM-EMBÊSeries

High Output Emergency Driver

The EM-EMB series emergency LED driver is for field and factory installation that allows up to 300W high output Sunled 0-10V dimmable fixtures to be used for both normal and emergency operation

The unit contains a battery charger and inverter that operates a load of 15W, 25W or 40W with constant power at a rated output voltage of 170VDC. The patented constant power circuitry of the module maintains uninterrupted illumination levels during power failure

Ê

Armour logos3

Ê

  1. PRODUCT VARIATIONS
  2. FEATURES
  3. SELF DIAGNOSTIC
  4. OPERATION
  5. SPECIFICATIONS
  6. APPLICATIONS
Ê
Product Code

Example EM-EMB cat. 15.WW

ÊMODEL NO WATTAGE TEST SWITCH
EM-EMB 15 15W/Up to 80W Driver WW Wired
25 25W/Up to 150W Driver WL 2.4GHz Remote
40 40W/Up to 300W Driver
Ê
NOTES
_ The emergency driver is not compatible with non-dimmable fixtures when the driver wattages is less than the fixture wattage.Ê
Ê
Features
Ê
  • Constant power output in emergency mode
  • Optimized for higher voltage LED luminaires with 170VDC driver input
  • Self-sensing output voltage circuitry maximises product compatibility
  • High temperature recyclable lithium battery technology for significantly decreased enclosure size and longer operational life
  • Rated for use in plenums, damp locations, enclosed and gasketed fixtures
Ê
Self Diagnostic
Ê
The integrated self-diagnostic circuitry will automatically conduct 1 monthly 30 second and annual 90 minute tests to verify proper emergency capability per life safety code requirements NFPA 101ÊLife Safety Code outlines the following schedule:
Ê
Monthly
During AC mode, the system conducts a 30s self discharge test of the emergency LED driver every 30 days and automatically restores to normal charging after full discharge
Ê
Annually
During AC mode, the system conducts a 90 minute self discharge test of the emergency led driver every 365 days and automatically restores to normal charging after 30 seconds discharge
Ê
Operation
Ê
Normal Supply
During normal AC supply conditions the LED driver load will operate as usual and emergency driver remains in charging mode
Ê
Emergency Mode
When AC power fails the driver automatically switches to emergency mode, keeping the LED load illuminated at a reduced lumen output for a minimum of 90 minutes. During this time, the indicator will flash slowly (light on for 2 seconds, off for 2 seconds). When AC power is restored, it will return to charging mode and the indicator light remains on
Ê
Specification
Ê
Input Voltage: 120-347VAC 50/60Hz
Input Power: 12W Max
Output Voltage: 170VDC
Output Power: 15,25,40W Power Factor: 0.85
EMI Radiated/Conducted: FCC Class A Charge and EM Modes
Surge Protection: Meets ANSI/IEEE C62.41.2-2002
Emergency Operation: 90 minutes
Charge Time: 24hr Recharge
Ambient Temperature: Lithium -25¡C to +40¡C (-13¡F to 104¡F)
Approval: cUL Listed for Factory and Field Installation