| Performance |
| Product Type | Linear Tube |
| Description | Field-adjustable power and color temperature double ended type B tubes with interchangable base type. |
| Wattage Equivalency | 59/86/96W Fluorescent |
| Input Wattage | 24/32/40W |
| Lumens | 3500/4400/5500lm |
| L70 Lifespan | 50,000-Hour LED lifespan based on IES LM-70 results |
| Electrical |
| THD | ≤25% |
| Power Factor | >0.9 |
| Dimmable | Yes, but not recommended for dimming applications. |
| Input Voltage | 120-277V |
| Operating Frequency | 50/60Hz |
| Input Current @ 120V (mA) | 200/278/353mA |
| Input Current @ 208V (mA) | 120/160/200mA |
| Input Current @ 240V (mA) | 105/140/175mA |
| Input Current @ 277V (mA) | 94/120/148mA |
| Operating Temperature | -4°F to 113°F (-20°C to 45°C) |
| LED Characteristics |
| Beam Angle | 210° |
| Color Temperature | Field adjustable via dip switch 3000/3500/4000/5000/6500K |
| Color Accuracy (CRI) | 82 CRI |
| R9 Value | High color performance with R9 greater than 0 |
| Color Consistency | <7-step MacAdam Ellipse binning to achieve consistent fixture-to-fixture color |
| Color Stability | LED color temperature is warrantied to shift no more than 200K in color temperature over a 5-year period |
| Color Uniformity | RAB's range of Correlated Color Temperature follows the guidelines of the American National Standard for Specifications for the Chromaticity of Solid State Lighting (SSL) Products, ANSI C78.377-2017. |
| Installation |
| Installation Method | UL Type B, Ballast Bypass |
| Base Type | Interchangable base: FA8 or R17D |
| Construction |
| Length | 8 ft |
| Shape | T8 |
| Finish | White |
| Endcap Material | Plastic |
| Enclosure Material | Glass |
| Lens Finish | Frosted |
| Compliance |
| Listings | UL Recognized, UL Classified |
| Environment | Suitable for use indoors in dry and damp environments. |
| Fixture Rating | Suitable for use in enclosed fixtures |
| Certification Model Number | T10277(T8-96G-DE-BYP) |
| California Title 20 Compliant | No |
| California Title 24 JA8 Compliant | No |
| California Energy Commission (CEC) Status | Lawful for Sales in California |
| NSF Listed | Meets NSF/ANSI standards for use in Food Zone (non-contact), Splash, and Non-Food Zones. Tube guard required in open fixtures. |
| Rohs | Mercury and UV free. RoHS-compliant components. |
| FCC | Complies with Part 15 of the FCC Rules |
| DLC Listed | This product is on the Design Lights Consortium (DLC) Qualified Products List and is eligible for rebates from DLC Member Utilities. Designed to meet DLC 5.1 requirements.DLC Product Code: S-SMHL8F |